SDEC Diesel Generator Set Technical Data
1.Power range:132KW
2.Alternator options:BOBIG/SDEC
3.Two types:open type and silent type
Engine:
1)Cooling method:closed water cooling
2)Starting method:electric start
3)Rated speed:1500rpm
Alternator
1)Brand:BOBIG
2)Rate output:132KW-145KW/165KVA-182KVA
3)Rate voltage:230V/400V
4)Rate frequency:50hz
5)Power factor:0.8
6)Phase:3-phase,4-wire
7)Connection:Y or other type connection
8)Excitation:harmonic excitation or phase comound or brushless
9)Voltage regulation:automatic/manual
Size
1)Open type:2370*950*1760
2)Silent type:3140*1200*1660
| General information | Prime power | Standby power | |||||||
| Rated Power (kVA) | 165 | 182 | |||||||
| Power Rating (kW) | 132 | 145 | |||||||
| Frequency (Hz) | 50 | ||||||||
| Engine Model | SC7H220D2 | ||||||||
| Engine Speed (RPM) | 1500 | ||||||||
| Phase | 3 | ||||||||
| PF | 0.8 | ||||||||
| Control System | Digital | ||||||||
| Rated voltage (V) | 400/230 (According to customer requirements) |
||||||||
| Fuel tank capacity operating time | ≥ 8h @ 75% load | ||||||||
| PRP:Prime power is available for an unlimited number of annual hours in variable load application,in accordance with GB/T2820-97; A 10% overload capability is available for a period of 1 hour within a 12-hour of operation | |||||||||
| ESP:The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption.No overload,utility parallel or negotiated outage operation capability is available at this ratin | |||||||||
| Dimension and Weight | |||||||||
| Model | BSD182 Open type |
BSD182S Silent type |
|||||||
| Length (L) mm | 2370 | 3140 | |||||||
| Width (W) mm | 950 | 1200 | |||||||
| Height (H) mm | 1760 | 1660 | |||||||
| Tank capacity (L) | 304 | 304 | |||||||
| Note: Specifications and illustrations are subject to revision without notice. | |||||||||
| Engine model & manufacturer | SC7H220D2(SDEC) | |||||||||||||
| Engine Model | SC7H220D2 | |||||||||||||
| Engine Type | In-line, 4 strokes, water-cooled; 4 valves, Turbo charged with aftercooler | |||||||||||||
| Combustion type | Direct injection | |||||||||||||
| Cylinder Type | Dry cylinder liner | |||||||||||||
| Number of cylinders | 6 | |||||||||||||
| Bore × stroke | 105 × 124 mm | |||||||||||||
| Displacement | 6.44 lit. | |||||||||||||
| Compression ratio | 16 : 1 | |||||||||||||
| Firing order | 1-5-3-6-2-4 | |||||||||||||
| fuel injection advance angle | 12°BTDC | |||||||||||||
| Dry weight | 600 kg | |||||||||||||
| Dimension | 1343x741x1267mm | |||||||||||||
| Rotation | CCW viewed from flywheel | |||||||||||||
| Fly wheel housing | SAE 3# | |||||||||||||
| Fly wheel | SAE 11.5#(number of teeth: 127) | |||||||||||||
| Injection pump | Longkou in-line “P” type | |||||||||||||
| Governor | Electric type | |||||||||||||
| Feed pump | Mechanical type | |||||||||||||
| Injection nozzle | Multi hole type | |||||||||||||
| Heavy duty diesel engine | Starter battery (with lead acid) including rack and cables | |||||||||||||
| Anti-vibration mount | Flexible fuel connection hoses | |||||||||||||
| Replaceable fuel filter, oil filter & air filter | Exhaust silencer and bellows | |||||||||||||
| Cooling radiator and fan | Operation manuals and circuit diagram documents | |||||||||||||
| Alternator | ||||||||||||||
| Alternator Brand | BOBIG | |||||||||||||
| Alternator Manufacturer | FUJIAN BOBIG ELECTRIC MACHINERY CO.,LTD | |||||||||||||
| Alternator Model | BW-274G | |||||||||||||
| Alternator Rated Power | 132kw/165kva | |||||||||||||
| Rated voltage (V) | 230v/400v | |||||||||||||
| Rated frequency | 50hz | |||||||||||||
| Connecting Type | 3 Phase and 4 W | |||||||||||||
| Number of Bearing | 1 | |||||||||||||
| Protection Grade | IP23 | |||||||||||||
| Altitude | ≤1000m | |||||||||||||
| Exciter Type | Brushless ,Self-exciting, AVR automatic voltage regulating,100% Copper | |||||||||||||
| Insulation Class | H class | |||||||||||||
| Telephone Influence Factor (TIF) | ≤50 | |||||||||||||
| THF | ≤2% | |||||||||||||
| Voltage Regulation, Steady State | ≤±1% | |||||||||||||
| Transient State Voltage | ≤-15%~+20% | |||||||||||||